Modbus
In Omnicomm Configurator, on the “Settings” tab select the “Modbus” section from the list:
Select the operation mode:
“Master” – terminal sends requests for the access to the registers from the external devices via Modbus protocol
“Listener” – terminal listens and receives the required data during the exchange via Modbus protocol
When is necessary to add parameters press the “Add” button. A window will open:
In the remote configuration server, in the “RS ports configuration” section, select the terminal operation mode and, if necessary, add the parameters by clicking the “Parameters configuration” button.
“Name of parameter” – enter the name of the parameter. Maximum length: 16 symbols.
“Address” – address of the tracked device. Possible values: 1 to 247.
“Function” – – enter the function number Possible values: 01 – Read coils, 02 – Read discrete inputs, 03 – Read holding registers, 04 – Read input registers.
“Register” – enter the register value. Possible values: 0 to 65535.
“Number of registers”. Possible values: for functions 1, 2 – from 1 to 64; for functions 3, 4 – from 1 to 4. Default value – 1.
“Time out” – enter the waiting time for the response of the device. Default value – 50 ms. Possible values: from 50…12500 ms.
“Value type” – select the data type. Possible values: S16, U16, S32, U32, U64, float, double, bin.
“Byte order” – select the order of words and bytes. Possible values: direct order of words and bytes, reverse order of words and bytes, reverse order of bytes, reverse order of words. Default value - direct order of words and bytes.
Maximum parameter number – 36.